NF Distribution Fuseboards SPN & TPN, 20A-200A

NF Distribution Fuseboards
This range of fully shrouded distribution fuseboards is suitable for systems with a rated insulation voltage up to 660V AC / 500V DC and is available in a sheet steel enclosure.

The range complies with BS 5486: Part 11 1989.

All ratings accept HRC bolt-in fuselinks to BS 88: Part 2. Fuselinks are not supplied.

The 20A and 32A NF units have removable end plates incororating conduit knockouts. Blank end plates can be supplied on request.

The 63A, 100A and 200A units have blank removable end plates.

NF Distribution Fuseboards 20A-200A

Current
Rating &

No. of

NF
Fuseboard

Suitable
Bill HRC

Dimensions (mm)

Polarity

Ways

Cat. No.

Fuselinks

H

W

D

20A
SPN

4

NFS204NLC

BNIT

386

304

148

6

NFS206NLC

BNIT

386

304

148

8

NFS208NLC

BNIT

386

368

148

12

NFS2012NLC

BNIT

386

448

148

20A
TPN

4

NFT204NLC

BNIT

631

304

148

6

NFT206NLC

BNIT

631

304

148

8

NFT208NLC

BNIT

631

368

148

12

NFT2012NLC

BNIT

631

448

148

32A
SPN

4

NFS304NLC

BTIA

386

304

148

6

NFS306NLC

BTIA

386

304

148

8

NFS308NLC

BTIA

386

368

148

12

NFS3012NLC

BTIA

386

496

148

32A
TPN

4

NFT304NLC

BTIA

710

304

148

6

NFT306NLC

BTIA

710

304

148

8

NFT308NLC

BTIA

710

368

148

10

NFT3010NLC

BTIA

710

448

148

12

NFT3012NLC

BTIA

710

496

148

63A
TPN

2

NFT602NLC

BTIS

546

473

227

4

NFT604NLC

BTIS

972

330

227

6

NFT606NLC

BTIS

972

330

227

8

NFT608NLC

BTIS

972

473

227

10

NFT6010NLC

BTIS

972

473

227

100A
TPN

2

NFT1002NLC

BTCP*

546

549

227

3

NFT1003NLC

BTCP*

1066

330

227

4

NFT1004NLC

BTCP*

1066

330

227

6

NFT1006NLC

BTCP*

1066

549

227

8

NFT1008NLC

BTCP*

1066

549

227

200A
TPN

2

NFT2002NLC

BTF

1560

410

270

3

NFT2003NLC

BTF

1560

410

270

4

NFT2004NLC

BTF

1560

529

270

6

NFT2006NLC

BTF

1560

529

270
* BTIA (2A-32A) of BTIS (40A-63A) fuselinks may be fitted by use of adaptor Cat. No. NF100LK.

Diversity Factors

No. of
Ways

Maximum Rated Current Per Way

200A

100A

63A

32A

20A

2

1.0

1.0

1.0

1.0

1.0

3

0.9

1.0

-

-

-

4

0.8

0.9

0.9

0.9

0.9

6

0.66

0.8

0.8

0.8

0.8

8

-

0.66

0.8

0.8

0.8

10

-

-

0.66

0.66

0.66

12

-

-

-

0.66

0.66

Therefore, Incomer Rating =

2

400A

200A

126A

64A

40A

3

540A

300A

-

-

-

4

640A

360A

227A

115A

72A

6

800A

480A

302A

154A

96A

8

-

528A

403A

205A

128A

10

-

-

416A

211A

133A

12

-

-

-

253A

160A

NF Distribution Fuseboard Accessories

Fuseboard
Current

Lid Locking
Cylinder
Type Lock

Lid Locking
Bracket &
Padlock

Spare Fuse
Carrier

Safety Fuse
Carrier

Rating

Cat. No.

Cat. No.

Cat. No.

Cat. No.

20A

NFLK1

-

94CARRIER

101CARRIER

32A

NFLK1

-

95CARRIER

102CARRIER

63A

NFLK1

-

96CARRIER

103CARRIER

100A

NFLK1

-

97CARRIER*

104CARRIER

200A

-

DLK4
+ PL1250

98CARRIER

105CARRIER
* BTIA (2A-32A) of BTIS (40A-63A) fuselinks may be fitted by use of adaptor Cat. No. NF100LK.
Adaptor clips (set of 2) enables the fitment of house service ferrule cap fuselinks to BS 1361.
Type IIa (60A)
NF63CL for 63A fuse carriers.
Type IIb (100A)
NF100CL for 100A fuse carriers.

NF Fuseboard Extended Outgoing Circuits

20A and 32A boards can be mounted side by side to extend outgoing circuits to 24 way maximum.

Additional shrouds (one per phase) are required when using looping facility Cat No. NF32CS.

All phase looping connections must pass through the same aperture. Apertures should be drilled in the positions shown.

NF Distribution Fuseboards Terminal Capacities

Current
Rating &

No.
of

Main
Terminal

Earth
Bar

Max. Terminal
Capacity mm²
(Copper Cables)

Outgoing
Terminal
Bore

Polarity

Ways

Stud Size

Main Stud

Outgoing

Main

Outgoing

Dia. mm.

20A
SPN

4

M10

M10

10mm²

95

6

4

6

8

120

12

20A
TPN

4

M10

M10

10mm²

95

6

4

6

8

120

12

32A
SPN

4

M10

M10

10mm²

95

16

5.5

6

8

150

12

32A
TPN

4

M10

M10

10mm²

95

16

5.5

6

8

150

10

12

63A
TPN

2

M12

M10

25mm²

240

35

8

4

6

8

M16

500

10

100A
TPN

2

M12

M10

25mm²

240

70

12

3

4

6

M16

500†

8

200A
TPN

2

M16

M10

70mm²

630*

150

18

3

4

6
* Cast cable socket, 1 hole fixing, suitable for 630mm² stranded copper conductors available separately to order. Cat. No. NF630SK.
Can be adapted to allow fitment of 2-240mm² maximum cable sockets with suitable copper spacing piece (set of 4). Cat. No. NF240SP.

Dimensions

NF Distribution Fuseboards 20A-200A

Current
Rating &

No. of

Dimensions mm

Approx.
Weight

Polarity

Ways

A

B

C

D crs

E crs

F dia.

Kg

20A
SPN

4

386

304

148

252

191

8

3.2

6

304

191

7.5

8

368

255

9.5

12

448

335

11.0

20A
TPN

4

631

304

148

442

191

8

13.4

6

304

191

14.4

8

368

255

17.4

12

448

335

20.9

32A
SPN

4

386

304

148

252

191

8

7.5

6

304

191

7.6

8

368

255

8.5

12

496

383

11.5

32A
TPN

4

710

304

148

576

191

8

13.7

6

304

191

14.2

8

368

255

18.7

10

448

335

22.2

12

496

383

24.2

63A
TPN

2

546

473

227

458

369

10

21.9

4

972

330

884

226

26.0

6

330

226

31.0

8

473

369

41.0

10

473

369

44.0

100A
TPN

2

546

549

227

458

445

10

28.9

3

1066

330

978

226

34.8

4

330

226

38.8

6

549

445

55.8

8

549

445

62.8

200A
TPN

2

1560

410

270

1334

206

10

78.0

3

410

206

91.0

4

529

325

107.0

6

529

325

123.0

Top | Home | E-mail