MCCB Panelboards & Moulded Case Circuit Breakers

'G' Frame Moulded Case Circuit Breakers
Talisman 'G' Frame MCCBs are available in ratings from 16A to 125A.

'G' Frame Standard Fixed
'G' Frame Hi-Break Fixed
'G' Frame Hi-Break Adjustable
'G' Frame MCCB Accessories

'G' Frame

The following table illustrates which MCCBs are suitable for which Talisman MCCB panelboard range, and gives an Frame size ratings and copper cable capacities of the outgoing MCCB.

Outgoing Moulded Case Circuit Breakers

Outgoing
MCCB

Talisman
Multi 1

Talisman
2

MPS
Range

Frame Size

Range

Range

Range

'G' Frame
16A - 125A
70mm²

Yes

No

Yes

'F' Frame
16A - 200A
120mm²

No

Yes

Yes

'J' Frame
160A - 250A
150mm²

No

No

Yes

'K' Frame
250A - 400A
240mm²

No

No

Yes
 

'G' Frame MCCBs Standard Range 16A - 125A
(70mm² copper cable capacity)
Suitable for
Talisman Multi 1 panelboards.

MCCB Description

Standard Range

Poles

1 Pole

3 Pole

Utilisation Category

A

A

Impulse Withstand

8kV

8kV

Adjustment
Thermal

Fixed

Fixed

Adjustment
Magnetic

Fixed

Fixed

Breaking Capacity IEC 60947-2 / BS EN 60947-2 (AC 50/60Hz)

380V AC/
415V AC

Icu (kA)
Ics (kA)

-
-

16
12

220V AC/
240V AC

Icu (kA)
Ics (kA)

16
12

25
13

250V DC

Icu (kA)
Ics (kA)

-
-

15
8

Current Rating (A)

1 Pole

3 Pole

Fixed Type
Standard Range

Cat. No.

Cat. No.

16A

TLG161

TLG163

20A

TLG201

TLG203

32A

TLG321

TLG323

40A

TLG401

TLG403

50A

TLG501

TLG503

63A

TLG631

TLG633

80A

TLG801

TLG803

100A

TLG1001

TLG1003

125A

TLG1251

TLG1253

Terminal Capacities
(max.)

70mm²

70mm²

Dimensions (mm)
 

A

25

75

B

138

138

C

71

71

D

87

87

Weight (kg) approx.

0.35

0.9

'G' Frame MCCBs Hi-Break Range 16A - 125A
(70mm² copper cable capacity)
Suitable for
Talisman Multi 1 panelboards.

MCCB Description

Hi-Break Range

Poles

1 Pole

3 Pole

Utilisation Category

A

A

Impulse Withstand

8kV

8kV

Adjustment
Thermal

Fixed

Fixed

Adjustment
Magnetic

Fixed

Fixed

Breaking Capacity IEC 60947-2 / BS EN 60947-2 (AC 50/60Hz)

380V AC/
415V AC

Icu (kA)
Ics (kA)

-
-

25
13

220V AC/
240V AC

Icu (kA)
Ics (kA)

25
13

35
18

250V DC

Icu (kA)
Ics (kA)

-
-

25
13

Current Rating (A)

1 Pole

3 Pole

Fixed Type
Hi-Break Range

Cat. No.

Cat. No.

16A

THG161

THG163

20A

THG201

THG203

32A

THG321

THG323

40A

THG401

THG403

50A

THG501

THG503

63A

THG631

THG633

80A

THG801

THG803

100A

THG1001

THG1003

125A

-

THG1253

Terminal Capacities
(max.)

70mm²

70mm²

Dimensions (mm)
 

A

25

75

B

138

138

C

71

71

D

87

87

Weight (kg) approx.

0.35

0.9

'G' Frame MCCBs Hi-Break Adjustable Range 18A - 125A
(70mm² copper cable capacity)
Suitable for
Talisman Multi 1 panelboards.

MCCB Description

Hi-Break Adjustable Range

Poles

3 Pole
(TP)

4 Pole*
(TPSN)

Utilisation Category

A

A

Impulse Withstand

8kV

8kV

Adjustment
Thermal

Adjustable

Adjustable

Adjustment
Magnetic

Fixed

Fixed

Breaking Capacity IEC 947-2 / BS EN 60947-2 (AC 50/60Hz)

380V AC/
415V AC

Icu (kA)
Ics (kA)

25
13

25
13

220V AC/
240V AC

Icu (kA)
Ics (kA)

35
18

35
18

250V DC

Icu (kA)
Ics (kA)

25
13

25
13

Current Rating (A)

3 Pole

4 Pole*

Fixed Type
Hi-Break Adjustable Range

Cat. No.

Cat. No.

18 - 25A

THGAT253

THGAT254

25 - 32A

THGAT323

THGAT324

32 - 45A

THGAT453

THGAT454

45 - 63A

THGAT633

THGAT634

63 - 85A

THGAT853

THGAT854

85 - 125A

THGAT1253

THGAT1254

Terminal Capacities
(max.)

70mm²

70mm²

Dimensions (mm)
 

A

75

100

B

138

138

C

71

71

D

87

87

Weight (kg) approx.

0.9

1.20
* Not suitable for use in Talisman panelboards.

Top | Home | E-mail

'G' Frame MCCB Accessories

Poles
Accessories

1 Pole
Cat. No.

2 Pole
Cat. No.

3 Pole
Cat. No.

4 Pole
Cat. No.

Terminal Shields

TTSG1

TTSG2

TTSG3

TTSG4

Blanking
Modules
(3 Pack)

-

-

TGBP1

-

Rotaty Drive
(Direct)

-

-

TRDG

TRDG

Rotaty Drive
(Extension Shaft)
*

-

-

TRDGVL

TRDGVL

Padlock
Attachment
(6 off)

TLLG1

TLLG1

TLLG1

TLLG1

Padlock

PL1252

PL1252

PL1252

PL1252

Interpole
Barriers
(one end set)

-

TIBG2

TIBG3

TIBG4

Spreader
Links

-

-

TSLFG3

TSLFG4
  User Fitted, Front Fitting Shunt Trips**

12V AC/DC
Coil Voltage

-

-

TSTG12

TSTG12

24V AC/DC
Coil Voltage

-

-

TSTG24

TSTG24

48V AC/DC
Coil Voltage

-

-

TSTG48

TSTG48

110-130V AC/DC
Coil Voltage

-

-

TSTG110

TSTG110

220-250V AC/DC
Coil Voltage

-

-

TSTG220

TSTG220

380-440V AC
50Hz
Coil Voltage

-

-

TSTG380

TSTG380
  User Fitted, Front Fitting Undervoltage Release**

12V AC 50Hz
Coil Voltage

-

-

TUVG12

TUVG12

24V AC 50Hz
Coil Voltage

-

-

TUVG24

TUVG24

48V AC 50Hz
Coil Voltage

-

-

TUVG48

TUVG48

110-130V AC
50Hz
Coil Voltage

-

-

TUVG110

TUVG110

220-240V AC
50Hz
Coil Voltage

-

-

TUVG220

TUVG220

380-440V AC
50Hz
Coil Voltage

-

-

TUVG380

TUVG380

12V DC
Coil Voltage

-

-

TUVG12D

TUVG12D

24V DC
Coil Voltage

-

-

TUVG24D

TUVG24D

48V DC
Coil Voltage

-

-

TUVG48D

TUVG48D

110-130V DC
Coil Voltage

-

-

TUVG110D

TUVG110D

220-250V DC
Coil Voltage

-

-

TUVG220D

TUVG220D
  User Fitted, Front Fitting Auxiliaries**

1 Gang
Changeover
Contacts

-

-

TAG1

TAG1
* Shaft for enclosure depth (min-max, mm) 140-280.
** Shunt trip and up to two auxiliary devices or UVR and up to two auxiliary devices can be fitted.
Includes self-interruption circuit via an integral mircroswitch.
Suitable for use as alarm switch or auxiliary switch - two switches may be fitted per MCCB.