'J'
Frame Moulded Case Circuit Breakers 160A - 250A
(150mm²
copper cable capacity)
Suitable for use with MPS Range. |
|
MCCB
Description |
Standard
Adjustable |
|
Poles |
3
Pole |
|
Utilisation
Category |
A |
|
Impulse
Withstand |
8kV |
Adjustment
Thermal |
0.8-1.0In |
Adjustment
Magnetic |
6.0-12.0In |
|
Breaking
Capacity IEC 60947-2 / BS EN 60947-2 (AC 50/60Hz) |
|
690V
AC |
Icu
(kA)
Ics (kA) |
14
7 |
|
480V
AC |
Icu
(kA)
Ics (kA) |
20
10 |
400V
AC/
440V AC |
Icu
(kA)
Ics (kA) |
35
18 |
|
380V
AC |
Icu
(kA)
Ics (kA) |
45
23 |
220V
AC/
240V AC |
Icu
(kA)
Ics (kA) |
65
33 |
|
250V
DC |
Icu
(kA)
Ics (kA) |
37
19 |
|
Current
Rating (A) |
3
Pole |
|
Range |
Cat.
No. |
|
160A |
TLJA1603 |
|
200A |
TLJA2003 |
|
250A |
TLJA2503 |
Terminal
Capacities
(max.) |
150mm² |
|
Dimensions
(mm) |
|
 |
A |
105 |
|
B |
254 |
|
C |
104 |
|
D |
126 |
|
Weight
(kg) approx. |
4.0 |
'J'
Frame MCCB Accessories
Poles
Accessories |
3
Pole
Cat. No. |
|
Terminal
Shields |
TTSJ3 |
Blanking
Modules
(3 Pack) |
TBPJ3 |
Padlock
Attachment
(6 off) |
TLLJ2 |
|
Padlock |