MCCB Panelboards & Moulded Case Circuit Breakers

Talisman Multi 1
A versatile range incorporating:

  • 3 - 18 triple pole outgoing ways
  • Outgoing 'G' Frame MCCBs up to 125A
  • Incomers up to 400A
  • Busbars available as 125A, 200A and 400A
  • Installer fitted incomers
  • Standard, Hi-break and Hi-break adjustable MCCBs

Talisman Multi 1 Panelboards

Busbar

Triple
Pole

Panelboard

Suitable
Incomer

Dimensions (mm)

Rating

Ways

Cat. No.

Frame Size

H

W

D

125A

3

TG203

'G'

450

700

162

200A

6

TG206

'F'

900

700

162

200A

12

TG212

F

1200

700

162

400A*

6

TG406

'J' or 'K'

1050

700

162

400A*

12

TG412

'J' or 'K'

1350

700

162

400A*

18

TG418

'J' or 'K'

1650

700

162
*400A panelboards are supplied with copper connecting links to suit 'J' frame incomers (Cat. No. TGCKJ) or 'K' frame incomers (Cat. No. TGCKK).

Select Installer Fitted Incomer

Talisman Multi 1 panelboards can be installer fitted with either MCCB or CBS (Circuit Breaker Switch) triple pole incomers.

Listed below are a selection of Installer fitted MCCB and CBS incomers.

Installer Fitted MCCB (Moulded Case Circuit Breaker)
Incomers for Talisman Multi 1 Panelboards

Current

'G' Frame
Standard

'F' Frame
Standard

'F' Frame
Standard
Adjustable

'J' Frame
Standard
Adjustable

'K' Frame
Standard
Adjustable

Rating

Cat. No.

Cat. No.

Cat. No.

Cat. No.

Cat. No.

100A

TLG1003

TLF1003

TLFA1003

-

-

125A

TLG1253

TLF1253

TLFA1253

-

-

160A

-

TLF1603

TLFA1603

TLJA1603

-

200A

-

TLF2003

-

TLJA2003

-

250A

-

-

-

TLJA2503

TLKA2503

320A

-

-

-

-

TLKA3203

400A

-

-

-

-

TLKA4003

Terminal
Capacities

70mm²

120mm²

120mm²

150mm²

240mm²

Weight
Kg.

0.9

2.1

2.1

4.0

5.4

Utilisation
Category

A

A

A

A

A

Impulse
Withstand
Voltage

8kV

8kV

8kV

8kV

8kV

Thermal
Adjustment

Fixed

Fixed

0.8-1.0In

0.8-1.0In

0.8-1.0In

Magnetic
Adjustment

Fixed

Fixed

6.0-12.0In

6.0-12.0In

6.0-12.0In

For further technical specification of incoming devices and outgoing MCCBs please select the following:

'G' Frame Outgoing MCCBs

'F' Frame MCCBs

'J' Frame MCCBs

'K' Frame MCCBs

Installer Fitted CBS (Circuit Breaker Switch)
Incomers for Talisman Multi 1 Panelboards
Fixed Magnetic Protection Only

Current

3 Pole

Frame

Magnetic
Takeover

Rated
Conditional
Short Circuit
Current

Rating

Cat. No.

Type

Current (A)*

Icc 415V AC

100A

TNF1003

'F'

1000A

25kA

125A

TNF1253

'F'

1250A

25kA

160A

TNF1603

'F'

1600A

25kA

200A

TNF2003

'F'

2000A

25kA

250A

TNJ2503

'J'

2500A

35kA

320A

TNK3203

'K'

3200A

35kA

400A

TNK4003

'K'

4000A

35kA
* ± 20%

Installer Fitted Direct Connection Lugs
for Talisman Multi 1 400A Panelboards
Cannot be used on TG203 panelboards

Incomer

Lugs

Type

Cat. No.

Incoming Lugs kit for 400A panelboards

TG4LK

Dimensions

Talisman Multi 1 Panelboards

Busbar

Triple
Pole

Panelboard

Dimensions (mm)

Rating

Ways

Cat. No.

A O/A

B

125A

3

TG203

450

300

200A

6

TG206

900

750

200A

12

TG212

1200

1050

400A

6

TG406

1050

900

400A

12

TG412

1350

1200

400A

18

TG418

1650

1500

Top | Home | E-mail